The Siemens MICROMASTER 440 Inverter 0.12kw - 250kw are frequency inverters for speed and torque control of three-phase motors. View and Download Siemens MICROMASTER 440 operating instructions manual online. 0,12 kW - 250 kW. MICROMASTER 440 Inverter pdf manual download. Also for: Micromaster 440 series.
- Siemens Inverter Micromaster 440 Manual
- Siemens Micromaster 440 Faults
- Siemens Vfd Micromaster 440 Manual
- Siemens Micromaster 440 Parameters
4 Communications
The Internet Archive is a bargain, but we need your help. If you find our site useful, we ask you humbly, please chip in. Thank you.— Brewster Kahle, Founder, Internet Archive. Sp-20 download manual.
Issue 10/06
MICROMASTER 440
24
Operating Instructions (Compact)
4 Communications
4.1 Establishing
communications
MICROMASTER 440
⇔ STARTER
The following optional components are additionally required in order to establish
communications between STARTER and MICROMASTER 440:
¾
PC <-> frequency inverter connecting set
¾
BOP if the USS standard values (refer to Section 6.4.1 'Serial Interface (USS)')
are changed in the MICROMASTER 440 frequency inverter
PC <-> frequency inverter connecting set
MICROMASTER 440
USS settings, refer to 6.4.1 'Serial
Interface (USS)'
STARTER
Menu, Options --> Set PG/PC interface
--> Select 'PC COM-Port (USS)' -->
Properties --> Interface 'COM1', select
a baud rate
NOTE
The USS parameter settings in the
MICROMASTER 440 frequency inverter
and the settings in STARTER must
match!
4.2 Establishing
communications
MICROMASTER 440
⇔ AOP
¾
Communications between AOP and MM440 are based on the USS protocol,
analog to STARTER and MM440.
¾
Contrary to the BOP, the appropriate communication parameters - both for the
MM440 as well as for AOP - should be set if the automatic interface detection
was not carried-out (refer to Table 4-1).
¾
Using the optional components, the AOP can be connected to the
communication interfaces (refer to Table 4-1).
Table 4-1
AOP at the BOP link
AOP at the COM link
MM440 parameters
- baud rate
- bus address
P2010[1]
–
P2010[0]
P2011
AOP parameters
- baud rate
- bus address
P8553
–
P8553
P8552
Options
- direct connection
- indirect connection
No option necessary
BOP/AOP door mounting kit
(6SE6400-0PM00-0AA0)
Not possible
AOP door mounting kit
(6SE6400-0MD00-0AA0)
6 Commissioning
Issue 10/06
MICROMASTER 440
28
Operating Instructions (Compact)
6 Commissioning
Siemens Inverter Micromaster 440 Manual
6.1 Quick
commissioning
The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)-
specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
Factory
setting
P0003 = 3
User access level *
1 Standard:Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)
Parameter filter
*
0 All parameters
2 Inverter
3 Motor
4 Speed sensor
P0010 = 1
Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory
setting
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
P0100 =..
Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default60 Hz
2 North America [kW], frequency default60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch
DIP50/60
determines the value of
P0100.
OFF =
kW, 50 Hz
ON =
hp, 60 Hz
Inverter application
(enters the required torque)
0 Constant torque (e.g. compressors, processing machines)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters
≥ 5.5 kW / 400 V
Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.
P010
0 =
1, 2
P010
0 =
0
START
P0004 = 0
0
1
0
Siemens Micromaster 440 Faults
P0300 =.. P0300 =..
P0205 =.. P0205 =..
1
Siemens Vfd Micromaster 440 Manual
0
0