The Siemens MICROMASTER 440 Inverter 0.12kw - 250kw are frequency inverters for speed and torque control of three-phase motors. View and Download Siemens MICROMASTER 440 operating instructions manual online. 0,12 kW - 250 kW. MICROMASTER 440 Inverter pdf manual download. Also for: Micromaster 440 series.

Advertising

4 Communications

The Internet Archive is a bargain, but we need your help. If you find our site useful, we ask you humbly, please chip in. Thank you.— Brewster Kahle, Founder, Internet Archive. Sp-20 download manual.

Issue 10/06

MICROMASTER 440

24

Operating Instructions (Compact)

4 Communications

4.1 Establishing

communications

MICROMASTER 440

STARTER

The following optional components are additionally required in order to establish
communications between STARTER and MICROMASTER 440:

¾

PC <-> frequency inverter connecting set

¾

BOP if the USS standard values (refer to Section 6.4.1 'Serial Interface (USS)')

are changed in the MICROMASTER 440 frequency inverter

PC <-> frequency inverter connecting set

MICROMASTER 440

USS settings, refer to 6.4.1 'Serial
Interface (USS)'

STARTER

Menu, Options --> Set PG/PC interface
--> Select 'PC COM-Port (USS)' -->
Properties --> Interface 'COM1', select
a baud rate

NOTE

The USS parameter settings in the
MICROMASTER 440 frequency inverter
and the settings in STARTER must
match!

4.2 Establishing

communications

MICROMASTER 440

AOP

¾

Communications between AOP and MM440 are based on the USS protocol,

analog to STARTER and MM440.

¾

Contrary to the BOP, the appropriate communication parameters - both for the

MM440 as well as for AOP - should be set if the automatic interface detection
was not carried-out (refer to Table 4-1).

¾

Using the optional components, the AOP can be connected to the

communication interfaces (refer to Table 4-1).

Table 4-1

AOP at the BOP link

AOP at the COM link

MM440 parameters
- baud rate
- bus address

P2010[1]

P2010[0]

P2011

AOP parameters
- baud rate
- bus address

P8553

P8553
P8552

Options
- direct connection
- indirect connection


No option necessary
BOP/AOP door mounting kit
(6SE6400-0PM00-0AA0)


Not possible
AOP door mounting kit
(6SE6400-0MD00-0AA0)

Advertising
Popular Brands
Popular manuals
Advertising

6 Commissioning

Issue 10/06

MICROMASTER 440

28

Operating Instructions (Compact)

6 Commissioning

Siemens Inverter Micromaster 440 Manual

6.1 Quick

commissioning

The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)-
specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.


Factory

setting

P0003 = 3

User access level *
1 Standard:Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)

Parameter filter

*

0 All parameters
2 Inverter
3 Motor
4 Speed sensor

P0010 = 1

Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory

setting

NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.

P0100 =..

Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default60 Hz
2 North America [kW], frequency default60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch

DIP50/60

determines the value of

P0100.

OFF =

kW, 50 Hz

ON =

hp, 60 Hz

Inverter application

(enters the required torque)

0 Constant torque (e.g. compressors, processing machines)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters

5.5 kW / 400 V

Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.

P010

0 =

1, 2

P010

0 =

0

START

P0004 = 0

0

1

0

Siemens Micromaster 440 Faults

P0300 =.. P0300 =..

P0205 =.. P0205 =..

1