I. Installation

Follow the installation illustration on the accompanying sheet.

4 Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 / M2-CA Operation Power Saving Display The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to darken after a period of inactivity.

Back-UPS Pro 1000 Installation and Operation 5 Warnings and System Faults Audible Warnings Warning Icons System Faults The Back-UPS will display these fault messages. For faults F01 and F02, contact APC Technical Support. Four Beeps Every 30 Seconds Back-UPS is running on battery. You should consider saving any work in progress. Back-UPS®Pro 1300/1500 Installation and Operation Connect the battery Install PowerChute® Personal Edition Software APC PowerChute Personal Edition software provides automatic file saving and shutdown of your computer in the event of a power failure. This addendum does not apply to Back-UPS Pro 1000/1400 and Smart-UPS V/S 1000/1400. Follow the installation illustration on the accompanying sheet. Note: Small sparks at the battery connectors are normal during connection. Once installed, allow the unit to charge for five hours. If the unit is an XL model.

Note: Small sparks at the battery connectors are normal during connection.

II.Post-Installation

Once installed,

allow the unit to charge for five hours. If the unit is an XL model, allow it to charge for

24 hours.

Note: The Smart-UPS will charge whether it is on or off, and will charge whether there is a load present or not. In situations where the power quality is poor, it is recommended that the unit be shutdown during this charging period. A Smart-UPS that is powered on may switch to battery operation which would prolong the time needed to fully recharge the battery.

III. Clearing the Replace Battery LED

A.In order for the replace battery LED to be cleared, it is necessary to run a valid self test. For a self test to be considered valid, the following conditions must be satisfied:

battery capacity must be greater than 75%(minimum of four battery bar graph LEDs illuminated) or

Smart-UPS must have been charging for at least 8 hours from the last low battery condition. (Low battery condition refers to a state when the Smart-UPS battery has fully discharged).

B.Ways to initiate a self test

A self test can be initiated in any one of five ways:

Start up of the UPS

Brother PT-15 P-touch Machine User's Manual. This Brother p-touch user's guide is a product download and the download link is provided below; file is in.pdf format. FILE SIZE: 3918k. Need Support? If you download the manual and still have questions, you can reach Brother's P. Brother P-Touch PT-15 Pdf User Manuals. View online or download Brother P-Touch PT-15 User Manual. Looking for a Brother MFC User Manual or DCP Operator Guide - we have those too! Our Brother P-touch label maker manual provides comprehensive instructions you can use to make the most of your label maker. And with quick, easy access to this guide on our website, you'll be able to make sure you’re using your label maker to its full potential. Brother p-touch pt-15 label maker user manual.

Smart-UPS front panel test button

Powerchute PLUS software

SmartSlot Accessory

Automatic timerevery two weeks from turn on (see APC owners manuals for details)

IV. Verifying Operation

A.What happens during a self test?

When a self test is initiated, the unit supports the load while operating on battery for approximately 8-10 seconds. During this period, the Smart-UPS determines the health of the battery.

B.When should the self test be performed?

1400

After the unit has charged for five hours, a self test can be performed.

C.What happens when the replace battery LED does not clear? If the self test fails:

Back Ups Pro 1000 Manual

If the battery capacity is greater than 75%, turn the unit off and restart it. When you turn a SmartUPS on, it will initiate a self-test. After the test completes, the LED should clear.

If the unit fails the self-test again, contact APC Customer Support (email: support.apcc.com or phone: 800-800-4APC).

V.Increasing ‘Runtime Remaining’ of the Smart-UPS as viewed through Powerchute PLUS or SmartSlot Accessory and prevent premature Low Battery Signal

Discharging and recharging a Smart-UPS resets the microprocessor to properly read battery voltage. An accurate measurement is important when calculating the runtime remaining value appearing in Powerchute PLUS or SmartSlot Accessory.

A.Initiating a runtime calibration

The runtime calibration option is accessible using Powerchute PLUS software or an APC SmartSlot Accessory. Once the battery capacity reaches 100%, select this option. The unit will run on battery until battery capacity is 25%. At that point, the unit will return to utility power and begin recharging itself. If the runtime as seen through Powerchute PLUS or SmartSlot Accessory does not increase, then follow the instructions in the next section.

Note: APC recommends that a runtime calibration be initiated once every six months at a maximum.

Pro

Back Ups Pro 1400 Manual

B.Disconnect from utility

And not the manufacturer. All warranties and support, if applicable, are with PDF Electric & Supply Inc. Allen bradley 1756 if8i user manual. PDF Electric & Supply Inc.

By disconnecting the UPS from utility, a premature low battery signal can be prevented. It is recommended that the power to the circuit be turned off at the distribution panel. Unplugging the Smart-UPS from the outlet is not recommended.

Note: The Smart-UPS will run on battery until it discharges completely, turning off the load. It is not necessary to discharge completely. Power can be restored to the unit once it reaches low battery condition(see owner’s manual for details on how to identify low battery condition).

If experiencing low runtime or premature low battery signal issues, contact APC Customer Support (email: support.apcc.com or phone: 800-800-4APC).

Apc Back-ups Pro 1400 User Manual